Industry · Equipment makers

Test bays for switchgear and panel makers

SUDHARSAN equips switchgear and panel factories with routine-test systems that keep pace with production: breaker trip testers, panel insulation withstand units and heavy-current sources for busbar temperature rise. Every panel is tested the same way, and customer witness tests pass the first time.

  • MCB & MCCB to 2000 A
  • Panel HV withstand
  • 4000 A temperature rise
What we solve

Outcomes for every role on the job

Production head

The test bay keeps pace with production.

QA engineer

Every panel tested the same way.

Customer inspector

Witness tests pass the first time.

Purchase

Kits built to the factory's own ratings.

Test-point explorer

Where we test in your factory

Pick a test to see where it is done and which SUDHARSAN kit proves it.

SUDHARSAN SI/MCB-MCCB 2-in-1 breaker test kit used for mccb overload and short-circuit release
Test point 1 · MCCB overload and short-circuit release

SI/MCB-MCCB

2-in-1 breaker test kit

Where
Final inspection of MCCB feeders
Rating
SI/MCB-MCCB 100/2000 (2-in-1)
View the SI/MCB-MCCB →
View all test points as a table
TestWhere in the factorySUDHARSAN kit
MCCB overload and short-circuit releaseFinal inspection of MCCB feedersSI/MCB-MCCB: SI/MCB-MCCB 100/2000 (2-in-1)
MCB and overload relay tripMCBs and motor-starter overload relaysSI/MCB-200: 0.01–200 A with timer
Panel insulation withstandCompleted LV panels before dispatchSI/HV series: SI/HV7: 3–10 kV
Busbar temperature riseBusbar systems and type verificationSI/PIK 4000 A: Heavy current source to 4000 A
RCCB / ELCB tripDistribution boards with RCCBsSI/RCCB-1T: With built-in timer
DC trip and closing coilsControl wiring, coils and DC relaysDC 300 V source: 0–300 V DC variable
FAQ

Frequently asked questions

How is an MCB trip tested in the factory?

Inject 1.13 × In (the MCB must hold), then 1.45 × In (it must trip within the conventional time), then the instantaneous multiple for its B, C or D curve. The SI/MCB-200 does all three with a built-in timer.

What HV test does a finished LV panel need?

A one-minute power-frequency withstand between live parts and the earthed frame at the voltage set for its insulation rating: for example, 1.89 kV for 690 V. The SI/HV7 covers this.

Can you supply a source for a 4000 A busbar temperature-rise test?

Yes. The SI/PIK heavy current source delivers up to 4000 A at 0–5 V and holds it steady until temperatures stabilise.

Trusted in equipment makers by
  • ABB
  • GE Power Controls
  • Larsen & Toubro
  • Alstom
  • Al-Ahleia Switchgears (Kuwait)
  • Aikah Electrical Industries (Dubai)
  • Meepco (Riyadh)
  • Lerbs AG (Germany)

Setting up or upgrading a test bay?

Send us your product ratings and daily volume, and we will design the bay.

Tell us your application. We’ll engineer the test solution. · Technical: +91 98847 01185 · anirudh@sudharsanelektric.com

WhatsApp +91 96558 62424